2308.16 REGCHM
Intended use
- Switching of 110 … 230 V AC or 24 V AC/DC electrical loads with floating contacts
- Mounting on DIN rail according to EN 60715 in distribution boxes
Product characteristics
- Manual switching of the relays is independent of the bus
- Operation as NO or NC contacts
- Logic operation and forcing function
- Switching feedback (bus operation only)
- Switch position display
- Central switching function with collective feedback
- Disabling function for each channel
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Integration into light scenes
- Operating hours counter, configurable via bus
- Input monitoring for cyclical updating with safety circuit
- No additional power supply necessary
- Current detection: measurement of the load current for each output
- Monitoring of threshold values for load monitoring, e.g. for reporting load drop-out
- Switching of capacitive loads and the resulting high switch-on currents
Technical data
KNX medium: | TP 256 |
Rated voltage KNX: | DC 21 … 32 V SELV |
Connection, KNX: | terminal |
Power consumption KNX: | typical 240 mW |
Power loss: | max. 8 W |
Ambient temperature: | −5 … +45 °C |
Storage/transport temperature: | −25 … +70 °C |
Mounting width: | 144 mm (8 rail units) |
Connection, outputs | |
Connection mode: | screw terminals |
single wire: | 1 x 0.5 … 4 mm² |
stranded without ferrule: | 1 x 0.5 … 4 mm² |
stranded with ferrule: | 1 x 0.5 … 2.5 mm² |
Current detection (sine) | |
Mains frequency: | 50/60 Hz |
Measuring range: | 0.25 … 16 A |
Accuracy (≤ 1 A): | ±100 mA |
Accuracy (> 1 A): | ±8 % of curr. val. |
Switching outputs | |
Contact type: | floating relay contacts (μ contact) |
Switching voltage AC: | AC 250 / 400 V |
Switching current 230 V AC1: | 16 A |
Switching current 230 V AC3: | 10 A |
Switching current 400 V AC1: | 10 A |
Switching current 400 V AC3: | 6 A |
Fluorescent lamps: | 16 AX |
Ohmic load: | 3680 W |
Capacitive load: | 16 A / 200 µF |
Switching voltage DC: | DC 12 … 24 V |
Switching current DC: | 16 A |
Min. switching current: | 100 mA |
Switch-on current 150 µs: | 600 A |
Switch-on current 600 µs: | 300 A |
Lamp loads | |
Incandescent lamps: | 3680 W |
HV halogen lamps: | 3680 W |
LV halogen lamps with | |
inductive transformers: | 2000 VA |
electronic transformers: | 2500 W |
Fluorescent lamps T5/T8 | |
non-compensated: | 3680 W |
parallel compensated: | 2500 W / 200 µF |
lead-lag circuit: | 3680 W / 200 µF |
Compact fluorescent lamps | |
non-compensated: | 3680 W |
parallel compensated: | 2500 W / 200 µF |
Mercury vapour lamps | |
non-compensated: | 3680 W |
parallel compensated: | 3680 W / 200 µF |
Approvals: | VDE |