23024 1S R
Intended use
- Switching of electrical loads with floating contacts
- Switching of electrically-driven blinds, shutters, awnings and similar hangings
- Mounting on DIN rail according to EN 60715 in distribution boxes
Product characteristics
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or via bus
- Central functions
- Cyclical monitoring
- KNX Data Secure compatible with ETS 5.7.3 or higher
- Can be updated with the ETS Service App
Characteristics switching operation
- Operation as NO or NC contacts
- Feedback function
- Logic operation and forcing function
- Central switching function with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Scene function
- Operating hours counter
Characteristics blinds operation
- Suitable for 230 V AC motors
- Operation modes ‘Blind with slats’, ‘Shutter/awning’, ‘Ventilation flap/skylight’
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Cyclical feedback during movement
- Forced position through higher-level controller
- Safety function: rain alarm, frost alarm, 3 independent wind alarms
- Sun protection function with auto Heating/Cooling
- Scene function
The total current of two adjacent outputs must not exceed 20 A.
Technical data
Ambient temperature: | −5 … +45 °C |
Storage/transport temperature: | −25 … +70 °C |
KNX | |
KNX medium: | TP 256 |
Rated voltage KNX: | DC 21 … 32 V SELV |
Current consumption KNX: | 4 … 24 mA |
Outputs | |
Switching voltage: | AC 250 V ~ |
Switching current AC1 (cos ϕ > 0.8): | 16 A |
Fluorescent lamps: | 16 AX |
Current carrying capacity | |
Neighbouring outputs: | Σ 20 A |
Loads per output | |
Ohmic load: | 3000 W |
Capacitive load: | 16 A / 140 µF |
Motors: | 1380 VA |
Switch-on current 200 µs: | max. 800 A |
Switch-on current 20 ms: | max. 165 A |
Lamp loads 230 V | |
Incandescent lamps: | 2300 W |
HV halogen lamps: | 2300 W |
HV LED lamps: | max. 400 W |
LV halogen lamps with | |
electronic transformers: | 1500 W |
inductive transformers: | 1200 VA |
Fluorescent lamps T5/T8 | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
lead-lag circuit: | 2300 W / 140 µF |
Compact fluorescent lamps | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
Mercury vapour lamps | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
Mounting width: | 216 mm (12 rail units) |
Connection, power supply and load | |
Connection mode: | screw terminals |
single wire: | 1 x 0.5 … 4 mm² |
stranded without ferrule: | 1 x 0.5 … 4 mm² |
stranded with ferrule: | 1 x 0.5 … 2.5 mm² |
KNX: | KNX bus connection block |