3361-1 M WW
Intended use
- Requirement-oriented control of lighting, room thermostats and other electrical loads in interior rooms
- Clamp mounting in suspended ceilings
- Ceiling installation on fixed ceilings in flush box according to EN 60670-1 with flush mounting set (ref.-no.: PMM-UP-SET-WW)
- Surface-mounted ceiling installation with surface mounting set (ref.-no.: PMM-AP-SET-WW)
Product characteristics
- Integrated bus coupling unit
- 3 PIR sensors
- Detection field 360°
- Integrated brightness sensor
- Deployed as presence detector, motion detector, or for alert operation
- Output functions: Switching, staircase function, switching with forced position, value transmitter, light scene extension, operating mode setting for room temperature controller
- Extension of the detection area by way of operating several devices as main unit or extension unit
- Adjuster for manual adjustment of sensitivity
- Status LED: Flashes during motion detection; depending on programming in normal operation or only during the walking test mode
Additional characteristics of “Universal” version:
- Manual operation with IR remote control possible (ref.-no.: KNX PM FB IR)
- 5 function blocks for motion detection each with 2 outputs
- Function blocks switchable, e.g. for day/night operation
- PIR sensors can be evaluated separately
- Brightness sensor function with 3 limiting values
- Light control with max. 3 channels, setpoint shift in operation, separate configuration of dimming-up, control and dimming-down phase
- Light control can be combined with presence detector function
- Temperature measurement
Presence detector function:
- Detection of the smallest motions e.g. at a workplace for detecting the presence of persons
- Switch on: Motion detection and brightness threshold not reached
- Switch off: No motion in the detection field and shut-off delay elapsed or brightness threshold exceeded
Motion detector function:
- Motion detection for passageways in buildings
- Switch on: Motion detection and brightness threshold not reached
- Switch off: No motion in the detection field and shut-off delay elapsed or brightness threshold exceeded
After reacting and switching on, the motion detection works independently of the brightness.
Signalling mode:
- Brightness-independent detection of motions in the detection field
- Switch on: After detection of an adjustable number of motions within the set monitoring period
- Switch off: No motion in the detection field and shut-off delay elapsed
Technical data
KNX medium: | TP 256 |
Rated voltage KNX: | DC 21 … 32 V SELV |
Current consumption KNX: | max. 10 mA |
Connection bus: | terminal |
Protection class: | III |
Ambient temperature: | −25 … +55 °C |
Storage/transport temperature: | −25 … +70 °C |
Relative humidity: | 10 … 100 % (no condensation) |
Protection level: | IP 44 |
Ceiling cut-out (Ø x D): | 44 x 35 mm |
Dimensions (Ø x H): | 53.5 x 38 mm (with design ring) |
Max. thickness of the suspended ceiling: | approx. 25 mm |
Installation depth: | min. 35 mm |
Distance between concrete ceiling and suspended ceiling: | min. 20 mm |
Design ring Ø inside: | 35.6 mm |
Design ring Ø outside: | 53.5 mm |
Profile height design ring: | 1.8 mm |
Profile height lens: | 5.5 mm |
Motion detection | |
Detection angle: | 360° |
Range: | Ø approx. 12 m (mounting height 3 m) |
Brightness sensor | |
Measuring range: | 10 … 2,000 lx |
Accuracy (≤ 80 lx): | ± 10 lx |
Accuracy (> 80 lx): | ± 5 % |
Accuracy (> 80 lx): | ± 5 % |