39001 1S U
Intended use
- Switching and dimming of lighting
- Reading in switching states of installation switches or push-buttons and other floating contacts at inputs 1…3
- Signal evaluation of condensation (ref.-no.: BTS 01) and leakage sensors (ref.-no.: LES 01) at inputs 1…3
- Acquisition of temperature values via NTC temperature sensor at input 3 (ref.-no.: FF 7.8)
- Installation in flush box according to EN 60670-1
Product characteristics
- Output can be operated via KNX telegrams or extension inputs
- Three extension inputs for connecting floating contacts or dew/leakage sensors. NTC temperature sensor can be connected to input 3.
- Supply via bus, no additional power supply necessary
- KNX Data Secure compatible with ETS 5.7.3 or higher
- Can be updated with the ETS Service App
Dimming operation characteristic
- Automatic or manual setting of the dimming principle suitable for the load
- Protected against no-load, short-circuit and overheating
- Signal in the event of a short-circuit
- Feedback of the switching position and the dimming value
- Parameterisable switch-on and dimming behaviour
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with pre-warning function
- Light scene operation
- Operating hours counter
- Power failure longer than approx. 5 seconds leads to switch-off of the dimmer actuator. Depending on the parameter setting, the connected load is calibrated after voltage return.
- Power extension possible by means of power boosters (ref.-no. ULZ 1755 REG)
Characteristics satellite input
- Operating functions switching, dimming (including colour temperature), controlling blinds, value transmitter (1 byte, 2 byte, 3 byte and 6 byte incl. RGBW und colour temperature presets), scene extension etc.
- Disabling function
- Debounce time adjustable
Logic function characteristics
- Logic gates
- Transformer (conversion)
- Disabling element
- Comparator
- Limit value switch
Technical data
Rated voltage: | AC 230 V ~ |
Mains frequency: | 50/60 Hz |
Power loss: | max. 1.5 W |
Stand-by power: | approx. 0.2 W |
Ambient temperature: | −5 … +45 °C |
Storage/transport temperature: | −25 … +70 °C |
Dimensions (W x H x D): | 48 x 50 x 28 mm |
KNX medium: | TP 256 |
Commissioning mode: | S-mode |
Rated voltage KNX: | DC 21 … 32 V SELV |
Current consumption KNX: | 5 … 18 mA |
Connection, KNX: | terminal connected to control cable |
Output | |
Connection mode: | screw terminals |
Rated voltage: | AC 230 / 240 V ~ |
The permissible load depends on the lamps connected and the type of load set. | |
Leading edge phase control | |
Incandescent / HV halogen lamps | 20 … 210 W |
Inductive transformers: | 20 … 210 VA |
Inductive transformers with LV LED: | 20 … 100 VA |
Dimmable HV LED lamps: | 1 … 32 W |
Trailing edge phase control | |
Incandescent / HV halogen lamps | 20 … 230 W |
Electronic transformers: | 20 … 230 W |
Electronic transformers with LV LED: | 20 … 200 W |
Dimmable HV LED lamps: | 1 … 200 W |
Reduction of load | |
for installation into wooden or hollow walls: | −15 % |
for installation into multiple combinations: | −20 % |
Connection | |
Connection mode: | screw terminals |
single wire: | 1 x 0.5 … 4 mm² |
stranded without ferrule: | 1 x 0.5 … 4 mm² |
stranded with ferrule: | 1 x 0.5 … 2.5 mm² |
Inputs | |
Control cable: | YY6x0.6 (preterminated) |
Input type: | floating contact |
Number: | 3 |
Total length of extension unit cable: | max. 10 m |
Cable type: | J-Y(St)Y (preferable) |
Voltage satellite inputs: | approx. 5 V |