FCA 2 REGHE
Product characteristics
- Connection of a fan coil unit with up to 6 fan speeds or connection of fan coil units with up to 3 fan speeds respectively
- Outputs can be operated manually, construction site mode
- Modes for heating, cooling or combined heating/cooling operations
- 2-pipe or 4-pipe operation
- Individual or hierarchical switching of fan speeds
- Feedback
- Disabling function for each channel
Operation modes
- Bus operation: operation via touch sensors or room controller
- Temporary manual control: manual operation locally with keypad, automatic return to bus operation
- Permanent manual control mode: only manual operation locally on device
Technical data
KNX medium: | TP 256 |
KNX supply: | DC 21 … 32 V SELV |
Power consumption KNX: | typical 150 mW |
Rated voltage: | AC 230/240 V ~, 50/60 Hz |
Power loss: | max. 3 W |
Ambient temperature: | −5 … +45 °C |
Storing temperature: | −25 … +70 °C |
Connection, KNX: | terminal |
Connection, mains and outputs | |
Connection mode: | screw terminals |
single wire: | 1 x 0.5 … 4 mm² |
stranded without ferrule: | 1 x 0.5 … 4 mm² |
stranded with ferrule: | 1 x 0.5 … 2.5 mm² |
Switch type: | NO contact |
Contact type: | floating relay contacts (μ contact) |
Switching voltage: | AC 230/240 V ~ |
Breaking capacity AC1: | 10 A |
Breaking capacity AC3: | 10 A |
Switching capacities per output | |
Ohmic load: | 2300 W |
Capacitive load: | 10 A / max. 140 µF |
Motors: | 1380 VA |
Lamp loads | |
Incandescent lamps: | 2300 W |
HV halogen lamps: | 2300 W |
LV halogen lamps with | |
inductive transformers: | 1200 VA |
electronic transformers: | 1500 W |
Fluorescent lamps | |
non-compensated: | 1000 W |
parallel compensated: | 1160 W / 140 µF |
lead-lag circuit: | 2300 W / 140 µF |
Approvals: | VDE |